The device can evaluate different temperature sensors. With P 0732 MON_MotorPTC the sensor fitted in the motor and the wiring variant are set (sensor cable routed in resolver or separate). In an evaluation via KTY, the shut-off threshold of the motor temperature can additionally be set.
Bild: Parameterization of temperature sensor
Parameters for function selection
P. no. |
Parameter name/ Setting |
Function |
---|---|---|
P 0731 | MON_MotorTemp_Max | Shut-off threshold for KTY |
(0) | Maximum sensor temperature X5 | Factory setting 100 degrees |
(1) | Maximum sensor temperature X5 | Factory setting 100 degrees |
P 0732 | MON_MotorPTC | Selection of sensor type |
(0) | OFF (0) | No evaluation |
KTY(1) | KTY84-130° | |
PTC(2) | PTC to DIN 44081 with short-circuit monitoring | |
TSS(3) | Klixon switch | |
PTC 1(4) | PTC to DIN 44081 without short-circuit monitoring | |
Not used(5) | Not assigned | |
NTC 220 (6) | NTC sensor 220 kΩ2) | |
NTC 1000 (7) | NTC sensor 1 MΩ2) | |
NTC 227 (8) | NTC sensor 32 kΩ2) | |
(1) | Connection | Termination variant |
X5(0) | Connection of the sensor to terminal X5 | |
X6/7(1) | Sensor connection is routed in encoder cable | |
X5_X6/7(2) | Use of both inputs possible | |
(2) | Off(0) | No evaluation |
KTY(1) | KTY84-130° | |
PTC(2) | PTC to DIN 44081 with short-circuit monitoring | |
TSS(3) | Klixon switch | |
PTC 1(4) | PTC to DIN 44081 without short-circuit monitoring | |
Not used(5) | Not assigned | |
NTC 220 (6) | NTC sensor 220 kΩ1) | |
NTC 1000 (7) | NTC sensor 1 MΩ1) | |
NTC 227 (8) | NTC sensor 32 kΩ1) | |
P 0733 | MON_MotorI2t | I1t characteristic setting |
(0) | Inom [%](0) | Rated current of the motor |
(1) | I0 [%](1) | First current interpolation point of motor protection characteristic: Maximum permissible standstill current |
(2) | I1 [%](2) | Second current interpolation point of motor protection characteristic referred to maximum characteristic current |
(3) | F1 [Hz](3) | First frequency interpolation point of motor protection characteristic |
(4) | FN / F(f) [Hz] (4) | Rated frequency |
(5) | Imax [%](5) | Max. overload current referred to rated motor current |
(6) | Time [sec](6) | Time for which the maximum current may be connected |
(7) | Ttherm | Set thermal time constant in seconds |
P 0735 | MON_MotorI2tType | Motor protection mode |
(-1) | Off(-1) | Protection disabled |
(0) | FREQU(0) | Motor frequency-dependent evaluation i(f), default setting |
(1) | THERM(1) | Evaluation with thermal time constant iTthThe thermal time constant is set via parameter P 0733.7 in [s]. The shut-off threshold based on measurement tolerances is 110% of the nominal value. |
Tabelle: Ixt setting
NOTE:
1) Does not apply to the ServoOne junior |