Up to rated speed the asynchronous motor runs with a full magnetic field and so is able to develop a high torque. Above rated speed the magnetic field is reduced because the maximum output voltage of the inverter has been reached and the motor is run in the so-called field-weakening range with reduced torque.
For field-weakening of asynchronous motors, the motor parameters must be known very precisely. This applies in particular to the dependency of the main inductance on the magnetizing current. It is essential to carry out a motor identification and an optimization in the basic setting range for field-weakening mode. In the process, default values for the control circuits and the "magnetic operating point" are set based on the rated motor data and the magnetizing current presetting in P 0340 CON_FM_Imag. Two variants are available for operation in field-weakening mode.
There are two variants for field-weakening of an asynchronous motor. The choice of variant 1 or 2 is made via parameter P 0435 CON_FM_FWMode.
Bild: Field weakening
Variant 1: (Table)
Combination of "pre-control via 1/n characteristic" + voltage controller. The motor identification sets the voltage controller so that the voltage supply in a weakened field is adequate. If the drive controller is at the voltage limit, it reduces the d-current and thus the rotor flux. Since the controller has only limited dynamism, and starts to oscillate if larger gain factors are set, it is possible to use variant 2.
Variant 2: (Calc)
Combination of "pre-control with modified 1/n characteristic (isd=f(n)) + voltage controller.
This characteristic describes the magnetizing current as a percentage of the nominal value of
P 0340 CON_FM_Imag dependent on the speed.
The choice between the modified 1/n characteristic and the static characteristic is based on parameter P 0341 CON_FM_ImagSLim.
P 0341 ≠ 0 signifies selection of the 1/n characteristic (default )
P 0341 = 0 signifies selection of the modified 1/n characteristic isd = f(n).
After a motor identification the voltage controller is always active, as the controller parameters are preset. With P 0345 CON_FNVConKp = 0 the voltage controller is deactivated.
Parameterizing variant 2:
Setting the d-current dependent on the speed. The speed is specified relative to the rated speed in P 0458 MOT_SNom, the d-current relative to the magnetizing current in parameter P 0340. Up to the field-weakening speed, a constant magnetizing current is injected
P 0340.
Voltage controller:
Vorgehensweise: Selection of modified characteristic
Example:
Index | P 0348 rated speed P 0340 Imageff |
P 0342 (0-7)Field-weakening speed in [%] | P 0343 (0-7)Magnetizing current in field-weakening mode in [%] |
---|---|---|---|
(0) |
Irated= 1800 rpm
Imag eff = 100% |
100 | 100 |
(1) | 110 | 100 | |
(2) | 120 | 100 | |
(3) | 130 | 100 | |
(4) | 140 | 90 | |
(5) | 150 | 70 | |
(6) | 160 | 55 | |
(7) | 170 | 0 |
Tabelle: Example of modified characteristic
Parameters
P. no. | Parameter name | Function |
---|---|---|
P 0340 | CON_FM_Imag | Effective value of the rated current for magnetization |
P 0341 | CON_FM_ImagSLim |
Field-weakening activation point (as % of For a synchronous machine this value must be set to 0. |
P 0342 | CON_FM_SpeedTab | Speed values scaled as % of P 0458 nrated to populate the modified table. |
P 0343 | CON_FM_ImagTab | d-current scaled as % of P 0340 Imag eff. to populate the modified table. |
Tabelle: Parameters for field-weakening
Copyright © LTi DRiVES GmbH, Januar 2013, ID-Nr.: 0842.26B.1-00 DE