Synchronous motors can also be operated above their rated speed at rated voltage, by reducing their voltage consumption based on on injection of a current component.
Features
Conditions
To effectively reduce the voltage consumption, the ratio of stator inductance P 0471 MOT_Lsig multiplied by the rated current P 0457 MOT_CNom to rotor flux P 0462 MOT_FluxNom must be sufficiently large. In contrast to field-weakening of asynchronous motors, synchronous motors can also be operated in the "field-weakening range" with full rated torque at the nominal value of the q-current. Power beyond the rated power output can therefore be drawn from the machine in field-weakening mode, even at rated current. This must be taken into consideration when configuring the motor.
Voltage demand
ATTENTION: If the speed achieved by field-weakening is so high that the induced voltage exceeds the overvoltage threshold of the device (for 400 V devices approximately 800 V, for 230 V devices approximately 400 V), this will result in destruction of the servocontroller if no additional external safety measures are applied. |
Field-weakening for the synchronous motor:
There are two variants for field-weakening of a synchronous motor. The choice of variant 1 or 2 is made via parameter
P 0435 CON_FM_FWMode.
Characteristic isd = f(n) | |
Calculated map | |
Voltage controller |
Bild: Field-weakening variants 1 and 2
Vorgehensweise: Variant 1: Characteristic isd = f(n) (Table)
Vorgehensweise: Variant 2: "Calculated map" (calc)
In the case of very rapid speed or load changes in the field-weakening range, the setting
P 0435 CON_FM_FwMode = 2 is selected. A characteristic for a higher control dynamism is calculated internally.
Features
The voltage controller overlaid over the map (setting as described in variant 1).
The set combination of voltage controller and map entails more commissioning commitment, but it enables the best stationary behaviour (highest torque relative to current) and the best dynamic response to be achieved.
Example
The speeds in P 0342 CON_FM_SpeedTab must continuously increase from index 0 -7.
Example:
Index | P 0348 rated speed P 0340 Imageff |
P 0342 (0-7)Field-weakening speed in [%] | P 0343 (0-7) Magnetizing current Isdref in field-weakening mode in [%] |
---|---|---|---|
(0) |
nrated= 1800 rpm
Imag eff = 100 % |
100 | 0 |
(1) | 110 | 55 | |
(2) | 120 | 70 | |
(3) | 130 | 90 | |
(4) | 140 | 100 | |
(5) | 150 | 100 | |
(6) | 160 | 100 | |
(7) | 170 | 100 |
Tabelle: Speeds in P 0342 CON_FM_SpeedTab
Parameters
P. no. | Parameter name | Function |
---|---|---|
P 0435 | CON_FM_FWMode | Selection mode for field-weakening of synchronous motors |
(0) | None | Field-weakening is off, regardless of other settings. |
(1) | Table | Field-weakening is effected by a characteristic which specifies the d-current dependent on the speed isd = f(n) P 0342 CON_FM_SpeedTab parameter and P 0343 Con_TAB_POSDelta. |
(2) | Calc | Field-weakening is effected by way of a characteristic which is set internally via the motor parameters. The d-current reference is then calculated dependent on the speed AND the required q-current: isd = f(n, isq_ref). The inaccuracies with regard to the motor parameters, the available voltage etc. can be compensated by way of the Scale parameter P 0436 CON_FW_SpeedScale. |
Tabelle: Selection mode for field-weakening
ATTENTION: When configuring projects, it must be ensured that the speed NEVER exceeds the value of the product of |