[DIALOG] Pre: Error or warning occured!\n\n Post: \n\nPress button\n "Continue", to reset error NOW or \n "Cancel", to reset error LATER (e.g. button "Reset"). \n\nNote:\n Errors with the a.m. reaction "RESET" can only be confirmed by\n switching off/on the device! [E1] 0: Error: CPU\nReaction: RESET\n\nCause:\n Processor defect or incorrect software version\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 6: Error: CPU\nReaction: RESET\n\nCause:\n Error in Cache-memory of serial EEPROM\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 8: Error: CPU\nReaction: RESET\n\nCause:\n Error in self test:\n Parameter initialization failed due to faulty parameter description\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 17: Error: CPU\nReaction: RESET\n\nCause:\n RAM area for scope functionality indequate\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 44: Error: CPU\nReaction: RESET\n\nCause:\n Timeout at parameter identification\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 55: Error: CPU\nReaction: RESET\n\nCause:\n Program memory data faulty\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. [E2] 1: Error: OFF\n\nCause:\n DC-link voltage < 212/425 V (also indicated at normal power-off)\n\nRemedy:\n Rectify power failure of connect higer mains voltage [E3] 0: Error: OC\n\nCause:\n Current overload due to\n 1. Incorrect parameter setting\n 2. Short, earth fault or insulation fault\n 3. Internal device defect\n\nRemedy:\n 1. Check parameters of control circuits\n 2. Check installation 19: Error: OC\n\nCause:\n Power stage protection initiated.\n Maximum allowed motor power exceeded\n depends on DC-link voltage and heat sink temperature.\n\nRemedy:\n 1. Check operating conditions of device\n 2. Reduce load 34: Error: OC\n\nCause:\n Ixt-shut-off below 5 Hz to protect power stage\n (permissible current/time area exceeded)\n\nRemedy:\n Reduce load 35: Error: OC\n\nCause:\n Current overload shut-off after wiring test\n Detected short, earth fault or insulation fault\n\nRemedy:\n 1. Check installation\n 2. Check motor insulation 41: Error: OC\n\nCause:\n Current overload due to hardware shut-off\n 1. Incorrect parameter setting\n 2. Short, earth fault or insulation fault during operation\n 3. Internal device defect\n\nRemedy:\n 1. Check parameter of control circuits\n 2. Check installation\n 3. Please contact your service provider if this error occurs again. [E4] 1: Error: OV\n\nCause:\n Voltage overload due to\n 1. Braking chopper overload (braked too long or too much)\n 2. Mains poer overload\n\nRemedy:\n 1. Set DECR ramp parameter lower, use ext. braking resistor or chopper\n 2. Adjust mains voltage [E5] 1: Error: OLM\n\Cause:\n I^2xt-shut-off to protect motor\n (permissible current/time area exceeded)\n\nRemedy:\n 1. Reduce load\n 2. Use higher-powered motor [E6] 1: Error: OLI\n\nCause:\n I^2xt-shut-off to protect power stage\n (permissible current/time area exceeded)\n\nRemedy:\n Reduce load [E7] 1: Error: OTM\n\nCause:\n Overheating motor (PTC in motor tripped) due to\n 1. PTC not connected or incorrect parameter setting\n 2. Overload of motor\n\nRemedy:\n 1. Allow motor to cool down\n 2. Connect PTC or check adjusment\n 3. Use a higher-powered motor [E8] 31: Error: OTI\n\nCause:\n Overheating of power stage due to\n 1. Ambient temperature too high\n 2. Load too high (power stage or bracking chopper)\n\nRemedy:\n 1. Improve ventilation\n 2. Use a higher-powered device\n 32: Error: OTI\n\nCause:\n Overheating in device interior due to\n 1. Ambient temperature too high\n 2. Load too high (power stage or braking chopper)\n\nRemedy:\n 1. Improve ventilation\n 2. Use a higher-powered device\n [E9] 1: Error: PLS\nReaction: RESET\n\nCause:\n Plausibility check detected invalid program sequence\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 4: Error: PLS\nReaction: RESET\n\nCause:\n Invalid sequence on controller initializing\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 6: Error: PLS\nReaction: RESET\n\nCause:\n Unknown switching frequency on initializing power stage protection\n\nRemedy:\n Please contact your service provider if this error occurs again. 8: Error: PLS\nReaction: RESET\n\nCause:\n Unable to initialize parameter list in device start-up phase.\n KP200 (at top left) or indication of parameter 423-ERPAR\n or the number of the faulty parameters.\n\nRemedy via reset of the device by means of:\n 1. DriveManager - active device -> reset to factory setting.\n 2. Switch-off device, hold down KP200 up and down key\n and switch-on deviced again. KP200 indicates "RESET" 9: Error: PLS\nReaction: RESET\n\nCause:\n Plausibility check detected invalid parameter object (incorrect data type\n or incorrect data length)\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 10: Error: PLS\nReaction: RESET\n\nCause:\n No readable parameter exists at the current user level\n or parameter access error via KP200\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 13: Error: PLS\nReaction: RESET\n\nCause:\n Both slots assigned the same module\n\nRemedy:\n 1. Remove a module.\n 2. Switch device off/on. 20: Error: PLS\nReaction: RESET\n\nCause:\n Error in auto-tuning\n\nRemedy:\n 1. Check match of motor rating plate data with corresponding motor parameters \n and re-start test and auto-tuning.\n 2. Please contact your service provider if this error occurs again. 33: Error: PLS\nReaction: RESET\n\nCause:\n Selected pre-setting does not converge with the parameter list\n\nRemedy\n 1. Install suitable firmware\n 2. Use other pre-setting\n 3. Please contact your service provider if this error occurs again. 48: Error: PLS\nReaction: RESET\n\nCause:\n Invalid sequence on macro processing\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 100: Error: PLS\nReaction: RESET\n\nCause:\n Internal parameter access error on controller initializing\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 101: Error: PLS\nReaction: RESET\n\nCause:\n No support to set lines per revolution of encoder\n\nRemedy:\n 1. Correction of lines per revolution (Parameter 432-ECLNC) 102: Error: PLS\nReaction: RESET\n\nCause:\n Unknown switching frequency on initialiszing PWM\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 121: Error: PLS\nReaction: RESET\n\nCause:\n No support to set lines per revolution of encoder\n\nRemedy:\n 1. Correction of lines per revolution (Parameter 474-EC2LN) 122: Error: PLS\nReaction: RESET\n\nCause:\n Incorrect configuration of connection X5\n (encoder simulation, encoder)\n\nRemedy:\n 1. Check adjustment of encoder or encoder simulation.\n 2. Please contact your service provider if this error occurs again. 250: Error: PLS\nReaction: RESET\n\nCause:\n Incorrect sequence of marker position of cam circuit\n\nRemedy:\n Set the positions in ascending sequency [E10] 0: Error: PAR\n\nCause:\n Invalid parameter setting\n\nRemedy:\n Correction of parameter setting or reset device to factory settin 7: Error: PAR\n\nCause:\n Value of one parameter is after start-up phase\n outside its value range.\n\nRemedy:\n Parameter 423-ERPAR contains the number of the faulty parameters, whose setting needs to be checked.\n 1. Switch device off/on\n 2. Correct source data set (offline) and store in device. 8: Error: PAR\n\nCause:\n Error in first initialization of parameter list.\n One parameter cannot reset to factory setting\n\nRemedy:\n Parameter 423-ERPAR contains the number of the faulty parameters, whose setting needs to be checked.\n 1. Switch device off/on\n 2. Please contact your service provider if this error occurs again. 9: Error: PAR\n\nCause:\n Error in initialization of a parameter with\n its stored adjustment.\n\nRemedy:\n Parameter 423-ERPAR contains the number of the faulty parameters, whose setting needs to be checked.\n 1. Switch device off/on\n 2. If this error occurs again, reset device to factory setting\n and store adjustment in device. 13: Error: PAR\n\nCause:\n The combination of the settings of the function selector\n for one of the analog inputs \n \nRemedy:\n Check and change adjustment 16: Error: PAR\n\nCause:\n Setting of parameter FOSA0 (function selector output OSA0)\n is outside its value range\n\nRemedy:\n Check and change adjustment 100: Error: PAR\n\nCause:\n Error in controller initialization\n\nRemedy:\n Check and change setting of control and motor parameters 101: Error: PAR\n\nCause:\n Error in initialization of encoder\n Resolver: Invalid number of pairs of poles for motor parameters\n\nRemedy:\n Check and change setting of encoder 102: Error: PAR\n\nCause:\n Error in initialization of modulation\n\nRemedy:\n Check and change setting of modulation 103: Error: PAR\n\nCause:\n Error in initialization of current control\n\nRemedy:\n Check and change setting of control and motor parameter 104: Error: PAR\n\nCause:\n Error in initializiation of speed calculation\n\nRemedy:\n Check and change setting of encoder 105: Error: PAR\n\nCause:\n Error in initialization of control task list\n\nRemedy:\n Check and change setting of control 106: Error: PAR\n\nCause:\n Error in initialization of torque calculation\n\nRemedy:\n Check and change setting of control and motor parameter 107: Error: PAR\n\nCause:\n Error in initialization of current models\n\nRemedy:\n Check and change setting of control and motor parameter 108: Error: PAR\n\nCause:\n Error in initialization of speed controller\n\nRemedy:\n Check and change setting of control and motor parameter 109: Error: PAR\n\nCause:\n Error in initialization of position calculation\n\nRemedy:\n Check and change setting of control and motor parameter 110: Error: PAR\n\nCause:\n Error in initialization of position control\n\nRemedy:\n Check and change setting of control and motor parameter 111: Error: PAR\n\nCause:\n Error in initialization of speed pilot control\n\nRemedy:\n Check and change setting of control and motor parameter 112: Error: PAR\n\nCause:\n Error in initialization of flux control\n\nRemedy:\n Check and change setting of control and motor parameter 113: Error: PAR\n\nCause:\n Error in initialization of voltage control\n\nRemedy:\n Check and change setting of control and motor parameter 114: Error: PAR\n\nCause:\n Error in initialization of voltage control\n\nRemedy:\n Check and change setting of control and motor parameter 115: Error: PAR\n\nCause:\n Error in initialization of flux control in FWR\n\nRemedy:\n Check and change setting of control and motor parameter 116: Error: PAR\n\nCause:\n Error in initialization of v/f characteristic line\n\nRemedy:\n Check and change setting of control and motor parameter 117: Error: PAR\n\nCause:\n Error in initialization of current/-voltage models\n\nRemedy:\n Check and change setting of control and motor parameter 118: Error: PAR\n\nCause:\n Error in initialization of control\n\nRemedy:\n Check and change setting of control and motor parameter 119: Error: PAR\n\nCause:\n Error in initialization of control\n\nRemedy:\n Check and change setting of control and motor parameter 120: Error: PAR\n\nCause:\n Error in initialization of encoder simulation\n\nRemedy:\n Check and change setting of connection configuraiton 121: Error: PAR\n\nCause:\n Error in initialization of connection X5\n (encoder/encoder simulation)\n\nRemedy:\n Check and change setting of connection configuration 122: Error: PAR\n\nCause:\n Error in initialization of connection X5\n (encoder/encoder simulation)\n\nRemedy:\n Check and change setting of connection configuration 131: Error: PAR\n\nCause:\n Error in initialization of testsignal for motor commutation\n Overflow of timer occured (maximum time 8.1 s) or selected current too large for device \n\n Reduce selected values for parameters IENCT and IENCC [E11] 0: Error: FLT\n\nCause:\n General error in floating point calculation\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. [E12] 6: Error: PWR\nReaction: RESET\n\nCause:\n Power pack not correctly identified\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. [E13] 1: Error: EXT\n\nCause:\n Error in external device\n\nRemedy:\n Rectify error in external device [E14] 0: Error: USR\n\nCause:\n Error in execution of a customer specific software function\n\nRemedy:\n 1. Check software version.\n 2. Please contact your service provider if this error occurs again. [E15] 150: Error: OP1\n\nCause:\n Error in module at option slot 1\n\nRemedy:\n 1. Check module and identifier\n 2. Please contact your service provider if this error occurs again. 151: Error: OP1\n\nCause:\n Error on option 1: BUS-OFF-condition identified\n\nRemedy:\n Check module contacting. If the error still occurs after switching\n off/on the device or module is defect. 152: Error: OP1\n\nCause:\n Error on option 1: Unable to send transmit-protocol.\n\nRemedy:\n Check module contacting. If the error still occurs after switching\n off/on the device or module is defect. 153: Error: OP1\n\nCause:\n Error on option 1: Module not longer responding\n\nRemedy:\n Check module contacting. If the error still occurs after switching\n off/on the device or module is defect. 154: Error: OP1\n\nCause:\n Error on option 1: Module signals error\n\nRemedy:\n Check module contacting. If the error still occurs after switching\n off/on the device or module is defect. [E16] 170: Error: OP2\n\nCause:\n Error in module at option slot 2\n\nRemedy:\n 1. Check module and identifier\n 2. Please contact your service provider if this error occurs again. 171: Error: OP2\n\nCause:\n Error on option 2: BUS-OFF-condition identified\n\nRemedy:\n Check module contacting. If the error still occurs after switching\n off/on the device or module is defect. 172: Error: OP2\n\nCause:\n Error on option 2: Unable to send transmit-protocol.\n\nRemedy:\n Check module contacting. If the error still occurs after switching\n off/on the device or module is defect. 173: Error: OP2\n\nCause:\n Error on option 2: Module not longer responding\n\nRemedy:\n Check module contacting. If the error still occurs after switching\n off/on the device or module is defect. 174: Error: OP2\n\nCause:\n Error on option 2: Module signals error\n\nRemedy:\n Check module contacting. If the error still occurs after switching,\n off/on the device or module is defect. 175: Error: OP2\n\nCause:\n Error on option 2: Module not initialized\n\nRemedy:\n Check module contacting. If the error still occurs after switching,\n off/on the device or module is defect. 176: Error: OP2\n\nCause:\n Error on option 2: Receive queue overflow\n\nRemedy:\n Increase cycle time of receive telegrams [E18] 11: Error: SIO\n\nCause:\n Watchdog for control of communication via LustBus tripped\n\nRemedy:\n 1.Check connection\n 2. Check busmaster or increase parameter SWDGT \n 3. Switch-off control (factory setting) with parameter SWDGT = 0 [E19] 0: Error: EEP\nReaction: RESET\n\nCause:\n Error accessing parameter memory\n\nRemedy:\n 1. Switch device off/on\n 2. Please contact your service provider if this error occurs again. 3: Error: EEP\nReaction: RESET\n\nCause:\n Error in writing the parameter memory\n\nRemedy:\n 1. Switch device off/on\n 2. Please contact your service provider if this error occurs again. 6: Error: EEP\nReaction: RESET\n\nCause:\n Error in reading the parameter memory during start-up phase\n\nRemedy:\n 1. Switch device off/on 2. Please contact your service provider if this error occurs again. 9: Error: EEP\nReaction: RESET\n\nCause:\n Error in writing a string parameter in parameter memory\n\nRemedy:\n 1. Switch device off/on\n 2. If this error occurs again, reset device to factory setting.\n 3. Please contact your service provider if this error occurs again. 18: Error: EEP\nReaction: RESET\n\nCause:\n Error of checksum in initialization of autosave-parameter\n\nRemedy:\n 1. Switch device off/on. Error will automatically be corrected.\n 2. Please contact your service provider if this error occurs again. 38: Error: EEP\nReaction: RESET\n\nCause:\n Error of checksum in initailization of device setting\n\nRemedy:\n 1. Switch device off/on\n 2. If this error occurs again, reset device to factory setting.\n and store adjustment in the device. [E21] 20: Error: SC\n\nCause:\n Error in auto-tuning\n\nRemedy:\n 1. Check motor wiring and repeat procedure.\n 2. Please contact Your service provider if this error occurs again. 21: Error: SC\n\nCause:\n Error in auto-tuning. Motor not connected or not properly connected\n\nRemedy:\n 1. Check motor wiring and repeat procedure.\n 2. Please contact Your service provider if this error occurs again. 22: Error: SC\n\nCause:\n Auto-tuning is only suitable for asynchronous machines.\n\n\nRemedy:\n Set parameter 153-CFMOT to ASM if an appropriate motor is used, and repeat auto-tuning. 23: Error: SC\n\nCause:\n Auto-tuning is unable to identify the connected motor correctly.\n\n\nRemedy:\n 1. Get motor parameters from manufacturer and enter manually\n 2. If possible use a different motor [E25] 47: Error: HWE\n\nCause:\n Hardware endswitch interchanged\n\nRemedy:\n Correction of endswitch wiring, or configuration\n of inputs of CDD3000 according to suppresion. [E26] 1: Error: OL5\n\nCause:\n Ixt-Shut-off below 5 Hz to protect power stage\n (Allowed current/time area exceeded)\n\nRemedy:\n Reduce load [E30] 0: Error: ENC\nReaction: RESET\n\nCause:\n Error in encoder interface\n\nRemedy:\n Check connection of encoder, cable type\n and parameter setting 1: Error: ENC\nReaction: RESET\n\nCause:\n Error in encoder interface:\n Identified breaking wire of tracksignal\n\nRemedy:\n 1. Check contact of encoder cable (motor/device)\n 2. Check encoder cable\n 3. Check cable type and parameter of encoder 123: Error: ENC\nReaction: RESET\n\nCause:\n Error in initialization of Hiperface-interface\n of encoder G6/G7:\n Encoder signals communication error\n\nRemedy:\n Check wiring and parameter setting 124: Error: ENC\nReaction: RESET\n\nCause:\n Error in initialization of Hiperface-interface\n of encoder G6/G7:\n Device signals communication error\n\nRemedy:\n Check wiring and parameter setting 125: Error: ENC\nReaction: RESET\n\nCause:\n Error in initialization of Hiperface-interface\n of encoder G6/G7:\n No support of encoder type with actual software\n\nRemedy:\n 1. Check type of encoder\n 2. Check software version 126: Error: ENC\nReaction: RESET\n\nCause:\n Error in initialization of Hiperface-interface\n of encoder G6/G7:\n Encoder signals malfunction (Detailed information: parameter 402-HSTAT)\n\nRemedy:\n Check encoder 127: Error: ENC\nReaction: RESET\n\nCause:\n Error in initialization of Hiperface-interface\n of encoder G6/G7:\n Communication parameter not found\n\nRemedy:\n Check wiring and parameter setting 129: Error: ENC\nReaction: RESET\n\nCause:\n Error in initialization of Hiperface-interface\n of encoder G6/G7:\n Motor was moved during initialization\n\nRemedy:\n Take care of standstill of motor during initialization of Hiperface-interface\n of encoder [E31] 30: Error: TIM\nReaction: RESET\n\nCause:\n Control of running time (undefined routine) triggered\n\nRemedy:\n 1. Switch device off/on.\n 2. Pleaes contact your service provider if this error occurs again. 30: Error: TIM\nReaction: RESET\n\nCause:\n Control of 5 ms running time triggered\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 41: Error: TIM\nReaction: RESET\n\nCause:\n Watchdog running time control (dSMC) triggered\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. [E32] 1: Error: FLW\n\nCause:\n Tracking error\n\nRemedy:\n 1. Reduce load or acceleration\n 2. Increase allowed tracking error [E33] 11: Error: WDG\n\nCause:\n Watchdog for RS232 (LustBus) triggered\n\nRemedy:\n 1. Check busmaster or increase 84-SWDGT [E34] 42: Error: VEC\nReaction: RESET\n\nCause:\n Error in initialization of dSMC-data-RAM\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 43: Error: VEC\nReaction: RESET\n\nCause:\n Error in initialization of dSMC-program-RAM\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. [E35] 1: Error: BRK\n\nCause:\n Error at output OSD03: \n 1. Breaked cable (I < 150 mA)\n 2. Kurzschluß\n 3. Short circuit\n\nRemedy:\n 1. Check wiring\n 2. Check load (Imin = 150 mA, Imax = 2,0 A)\n 3. Check voltage supply [E36] 0: Error: POS\n\nCause:\n Error in positioning and process control\n Please contact your service provider 210: Error: POS\n\nCause:\n Positive hardware endswitch starts in positioning 211: Error: POS\n\nCause:\n Negative hardware endswitch starts in positioning 212: Error: POS\n\nCause:\n Positive software endswitch starts in positioning 213: Error: POS\n\nCause:\n Negative software endswitch starts in positioning 214: Error: POS\n\nCause:\n Reference point not defined or found\n\nRemedy:\n 1. Check connection and position of reference cam\n 2. Check parameters of reference run 215: Error: POS\n\nCause:\n Error in access to optional hardware\n\nRemedy:\n Check contact and parameters of optional hardware 216: Error: POS\n\nCause:\n Error in positioning and process control:\n Selected program not yet available\n\nRemedy:\n Check parameter of program selection 217: Error: POS\n\nCause:\n Error in positioning and process control:\n Jumps to an unavailable setnumber\n\nRemedy:\n Check syntax of program in process program editor 218: Error: POS\n\nCause:\n Error in positioning and process control:\n Called sub-program not available\n\nRemedy:\n Check syntax of program in process program editor 219: Error: POS\n\nCause:\n Target position is outside of positioning range\n\nRemedy:\n 1. Check positioning range\n 2. Check adjustment of endswitches 220: Error: POS\n\nCause:\n Error in positioning and process control:\n Division by zero 221: Error: POS\n\nCause:\n Error in positioning and process control:\n Max. nesting depth (10) exceeded\n\nRemedy:\n Check syntax of programm in process program editor 223: Error: POS\n\nCause:\n Target position not reached\n\nRemedy:\n 1. Check positioning range\n 2. Check load\n 3. Check positioning window (axis in position) 224: Error: POS\n\nCause:\n Loss of enabling advance travel\n\nRemedy:\n 1. Set enable advance travel, (if parameter set)\n 2. Control released 225: Error: POS\n\nCause:\n Do not activate (automatic/reference run/inching mode), \n Conflict of control location 226: Error: POS\n\nCause:\n Error in positioning and process control\n Index overflow (indicate addressing)\n\nRemedy:\n Check syntax of program in process program editor 232: Error: POS\n\nCause:\n Error in positioning and process control:\n Error in reading parameter\n 1. Reading failed or \n 2. the parameter is not readable\n\nRemedy:\n Check validity of parameter (number, value, access condition) 233: Error: POS\n\nCause:\n Error in positioning and process control:\n Error in writing a parameter\n 1. Writing failed or\n 2. the parameter is not writable\n\nRemedy:\n Check validity of parameter (number, value, access condition) 234: Error: POS\n\nCause:\n Error in processing a touchprobe process order 235: Error: POS\n\nCause:\n Error in positioning and process control:\n Order during axis movement not allowed (e.g. SAVE)\n\nRemedy:\n Wait for axis standstill or deactivation of control 236: Error: POS\n\nCause:\n Hardware endswitch interchanged\n\nRemedy:\n Correction of wiring endswitches or configuration \n of inputs of CDD3000 according to the suppression. [E37] 50: Error: FLH\nReaction: RESET\n\nCause:\n Error in data-flash-memory:\n TimeOut in delete process\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 51: Error: FLH\nReaction: RESET\n\nCause:\n Error in data-flash-memory:\n One sector defect, writing failed\n\nRemedy:\n 1. Switch device off/on.\n 2. Please contact your service provider if this error occurs again. 57: Error: FLH\nReaction: RESET\n\nCause:\n Error in data-flash-memory:\n Identified faulty sector in start-up phase\n\nRemedy:\n 1. Reset device to factory setting\n 2. Switch device off/on.\n 3. Please contact your service provider if this error occurs again. [E38] 45: Error: HW\n\nCause:\n Left hardware endswitch starts 46: Error: HW\n\nCause:\n Right hardware endswitch starts [E39] 47: Error: HWE\n\nCause:\n Hardware endswitch interchanged\n\nRemedy:\n Correction of endswitch wiring or configuration\n of CDD3000 inputs according to suppression. [E40] 0: Warning: WRN\n\nCause:\n Signal warning not defined.\n Please contact your service provider. 59: Warning: WRN\n\nCause:\n The adjusted max. torque (parameter TCMMX, function msk limit values)\n is larger than the maximum rtorque, can be reached with the motor or device.\n\nPlease note:\n The max. torque was suited automatically.\n Check the new adjustment. 60: Warning: WRN\n\nCause:\n While initialisation of field modell motor data check has failed \n Please check motor data: \n Main inductivity is too large for device ? \n Motor current much smaller than device current ? \n 61: Warning: WRN\n\nCause:\n The position reference exceeds in connection with\n your distance scaling the allowed value range.\n\nPlease note:\n The maximum position range was limited automatically.\n Check the scaling (function mask basic setting scale)\n or the selected position reference. 62: Warning: WRN\n\nCause:\n The set maximum speed (parameter SCSMX, function mask limit values)\n is larger than the maximum speed, reached with the motor.\n\nPlease note:\n The max. speed was suited automatically.\n Check the new adjustment. 63: Warning: WRN\n\nCause:\n The selected positioning speed or acceleration exceeds\n in connection with your scaling the allowed value range.\n\nPlease note:\n Speed resp. accelereation was limited automatically.\n Check your scaling (function mask basic setting scale)\n or the selected speed resp. acceleration. 80: Warnung: WRN\n\nCause:\n Warning in execution of a customer specific software function 81: Warnung: WRN\n\nCause:\n Warning in execution of a customer specific software function 177: Warning: WRN\n\nCause:\n Error counter of the CAN controller is reached